M-Bus Electricity Sub-Meters for the Outbuildings

I’ve been finding the electricity sub-meters in the House very useful, showing the electrical consumption of the ‘significant’ electrical loads as a proportion of the total recorded by the main electricity meter, so I’ll be adding some in the Outbuildings too.

For the House, I initially used cheap meters with only an S0 ‘pulse’ output and recorded the readings manually every month. Later, I found some affordable (second-hand) M-Bus adaptors for the ‘pulse’ meters (various models from the Relay Padpuls range) and added those, enabling the meters to be included in the once-per-minute reading cycle for the Water meters and the Heat meters.

The ‘significant’ loads that in my view warrant a dedicated sub-meter are:

  • Heat Pumps
    • In conjunction with a Heat Meter for heat pumps with a Water output, enabling the real-world efficiency to be calculated
    • With an Air-to-Air heat pump, as will be installed in the Outbuildings, it’s not practical to measure the heat output – but it’s still worth recording the electricity input
    • If there are secondary circulation pumps or control units which have a separate electrical supply from the main Heat Pump unit, these should ideally have their own sub-meter
  • Mechanical Ventilation (with or without Heat Recovery) Systems
    • While their consumption is not especially high, the fact that these typically run 24×7 means their total usage can add up – and since they’re still quite unusual in UK homes it’s good to track their actual energy consumption
    • Some MVHR units vary their fan power to provide a consistent airflow, in which case a gradual increase in energy consumption can be an indication that the filters need replacing – although normally the filters should be replaced before this increase becomes noticeable
  • Electric Vehicle Charge Points
    • Sometimes these incorporate their own electricity metering, which can be accessed via a Smartphone App or other interface, but it’s convenient to have them metered in the same way as the other electrical loads
    • Each charge point should have its own meter, should there be more than one
  • Other ‘large’ or ‘interesting’ loads
    • Immersion heaters
    • Rainwater harvesting pumps

There’s a wide choice of electricity meters with an S0 ‘pulse’ output (EN 62053-31) and a rather smaller choice of meters with a Modbus output. For meters with a native M-Bus (Meter-Bus) output the choice is smaller still – but for a building that needs to have some M-Bus metering anyway it’s much more straightforward to add further M-Bus meters than to cater for alternative metering protocols as well.

I’ve settled on using MID-certified M-Bus meters from UK company Rayleigh Instruments, having added one of their meters to the House a few months ago and after receiving positive feedback from another self-builder who uses one for their air-to-water Heat Pump:

  • The 2-module-wide RI-D35-100-MB which is a directly-connected meter for loads up to 100A
    • This reports Manufacturer = “RAY” which is one of two manufacturer codes allocated to “Rayleigh Instruments, United Kingdom”
    • This returns a lot of data via M-Bus which spills over into a second M-Bus telegram, requiring the M-Bus software to be able to handle a multi-telegram response
  • The 1-module-wide RI-D175-MB which is a directly-connected meter for loads up to 45A
    • Despite being branded as a Rayleigh Instruments unit, this reports Manufacturer = “PAD” which is a manufacturer code allocated “PadMess, Germany”
    • Note that this meter appears not to respond to a Secondary M-Bus address, so Primary addressing must be used
    • There’s a variant of this available with a Current Transformer (CT) input instead of being directly-connected, which caters for currents up to 100A
    • There’s more information about this specific meter in a Technical Article page here.

These are available for about £25 each; surprisingly the larger meter is less than 10% more expensive than the smaller one, so actually I only use the smaller one for loads up to about 16A (where the smaller terminals are helpful for connecting smaller-section cables) and use the larger one for loads like the EV charge points, where the load won’t even exceed 32A.

The Rayleigh meters are shipped with their Primary M-Bus address set to ‘0’ (RI-D35-100-MB) or ‘1’ (RI-D175-MB) so if the intention is to extract readings using the Primary rather than the Secondary M-Bus addresses, these need to be changed from the default. This can be accomplished using one of the utilities shipped as part of the libmbus codebase:

$ mbus-serial-set-address -b 2400 /dev/ttyUSB0 old_primary_address new_primary_address

Outbuildings: Week 21, Day 5

Outbuildings: Week 21, Day 5

Installation of the vertical, threaded sections of the rise-and-fall gutter brackets then the start of the installation of the roof tiles. The lower section of the tiles at the North end of the Workshop is the only area that needs about a metre of lead flashing, which meant cutting out the horizontal mortar joints ready to seat the lead into.